Description & Features:

• Approved for intrinsically-safe applications in Class 1/Div. 1 hazardous areas

• Rugged stainless steel construction with ceramic sensor

• Available ranges include in/Hg up to 8,700 psi

• Wide range of mechanical and electrical connections

• 0.5% FSO accuracy

• NEMA 4X and 6P / IP65, IP67 and IP68

• Approved for outdoor use

• Customizable

Output Signal Standard 2-wire: 4-20 mA / Vs = 8-32 Vdc I.S. protection: Vs = 14-28 Vdc Optional 3-wire: 0-20 mA / Vs = 14-30 Vdc 0-10 V / Vs = 14-30 Vdc
Accuracy ±0.5% FSO IEC 60770
Permissible Load Current 2-wire: Rmax = [(Vs – Vs min) / 0.02] Ohm Current 3-wire: Rmax = 500 Ohm Voltage 3-wire: Rmin = 10 k Ohm
Influence Effects Supply: 0.05% FSO / 10 V Load: 0.05% FSO / k Ohm
Response Time ≤10 ms
Thermal Error ≤±0.2% FSO / 10K In compensated range: -13°F to 185°F (-25°C to 85°C)
Permissible Temperatures Medium: -40°F to 257°F (-40°C to 125°C) Electronics environment: -13°F to 185°F (-25°C to 85°C) Storage: -40°F to 212°F (-40°C to 100°C)
Short-circuit Protection Permanent
Reverse Polarity Protection No damage. No function.
Electromagnetic Protection Emission and immunity according to EN 61326
I.S. Protection Class 1, Div. 1, Groups A, B, C & D
Stability Vibration: 10 g RMS (25 to 2,000 Hz) Shock: 500 g / 1 ms
Pollution Degree 4, electrical equipment for outdoor use
Housing 316L SS
Pressure Port 316L SS
Wetted Parts Seals: PN < 1,450 psi: FKM70. Others available. PN > 1,450 psi: FKM90. Others available. Diaphragm: Ceramic AI2O3 96%
Winters LIS Intrinsically Safe Transmitter