The Incus is an advanced ultrasonic gas leak detection system utilizing four ultra-sensitive acoustic sensors which constantly monitor wide areas for ultrasound generated from the release of pressurized gas. Ideally suited for monitoring well ventilated outdoor environments, the Incus ultrasonic detector has been engineered to withstand even the most extreme conditions and is unaffected by inclement weather, wind, leak direction, and gas dilution or stratification.
Detection frequency range | 25 kHz to 100 kHz |
Dynamic range | 40–120 dB (standard); 58–104 dB or 40–200 dB |
Area coverage | 2 to 20 meters (7 to 65 feet) radius (leak pressure, size and background level dependent) |
Response time | Instantaneous (< 1 s – speed of sound) |
Programmable alarm delay | Configurable alarm delay via one second increments |
Operating temperatures | -40 °C to +85 °C (-40 °F to +185 °F), option -55 °C (-67 °F), NOT c FM us approved |
Operating humidity range | 0 to 100 % relative humidity, non-condensing |
Self test | Continuous electronic check of sensor integrity |
Ingress protection | Rated IP66/67 & NEMA Type 4X to withstand harsh environments |
Enclosure material | AISI 316 stainless steel |
Mounting bracket | AISI 316 stainless steel (included) |
Weight (with bracket) | 18 kg (40 lb) |
Conduit entry | ½ in. or ¾ in. NPT available as single entry (all listings) or M20/M25 single entry and all dual entry (all listings EXCEPT FM) |
Output signals | Analog [0 mA: zero/low power, 0.5 mA to 4.0 mA: detector faults, 4–20 mA] Two form C relay contacts [Error/fault, alarm, maintenance] HART® protocol |
Approvals/classifications | IECEx ITS 10.0004X ATEX Ex d ib IIB+H2T4 Gb (Tamb -40 °C to +85 °C); (Tamb -55 °C to +85 °C) option c FM us CL1 Division 1, GP B, C, D T4 CL1 Zone I, AEx/Ex d ib IIB+H2 T4 EAC RU C-GB.ГБ04.B.00297 KOSHA: 14-KB4BO-0294X INMETRO UL-BR 15.0063X ABS: 13-LD1021861 DNV: A-13745 SIL 2 suitable EMC: EN 50270 2006, EN 61000-6-3 2007, EN 61000-6-2 2005 |
Input voltage | 24 Vdc (15 to 30 Vdc) |
Power consumption | 6 W – standard operation |