The CCO 5500 Carbon Monoxide (CO) Analyzer uses infrared absorption spectroscopy to continuously measure CO concentration in combustion flue gases. The infrared source is mounted directly on the flue gas duct or stack on the side opposite from the receiver. Infrared energy is radiated by the source, through a chopper across the duct to the receiver. The receiver employs gas filter correlation and narrow band-pass optical filtration with two solid state detectors to determine the absorption of radiation by CO in the flue gas.

Measurement Range Selectable 0-100 ppm to 0-10,000 ppm within the range of 200 to 6,000 ppm.m
Accuracy ± 2% of measurement or ± 5ppm whichever is greater
Path Length 0.5 to 8 m
Process Temperature Range 0 to 650 °C – at temperatures above 300 °C instrument accuracy will deteriorate
Ambient Temperature Range -20 to 70 °C
Communication Protocol 4-20 mA
Power requirements 110/220 Vac, 50/60 Hz
control module display/keypad English
calibration options Calibration check cell and holder
Rosemount™ CCO 5500 Carbon Monoxide (CO) Analyzer